Skip to main content

Installation

Before installation

WARNING: Read this manual carefully before installing and operating the SMD4. Observe the following safety instructions.

Qualified personnel

WARNING: All work described in this document may only be carried out by persons who have suitable technical training and the necessary experience or who have been instructed by the end-user of the product.

WARNING: Without proper training and necessary experience, damage to the equipment or personal injury might result.

DANGER: Danger of electric arcing! Never plug or unplug any connector while powered. Plugging or unplugging a motor while powered may damage or destroy the driver output stage.

Additional safety and warning notices.

Unpacking

On receipt of the instrument remove all packing material and check that all items on the delivery note have been received. Report any damage or shortages to the company or distributor who supplied the instrument. The packing material has been specially designed to protect the instrument and should be retained for possible future use.

Mechanical installation

The SMD4 is freestanding instrument. It does not require mounting. Forced air ventilation is not required. The ambient operating temperature range is 10 °C to 60 °C.

Connecting

Rear panel

SMD4 Rear flat render.JPG

Power

Connector: Barrel power jack

2.1 mm pin, 5.6 mm hole


image.png

48 Vdc input. Centre positive.


Power input for both internal logic circuits and the motor itself.

The power supply must meet the following requirements:

  • 48 V DC regulated supply, 48 W minimum
  • Reinforced or double insulation between mains and supply output

DANGER: Danger of electric arcing! Never plug or unplug the connector while powered.

CAUTION: In the event of reverse polarity, a short circuit will occur between GND and V+ through an internal power diode. An external fuse may be required.

The fuse should be sized:

  • Greater than the current consumption of the SMD4 when operating the connected motor
  • Less than the maximum current output of the power supply
  • Considering the voltage of the supply

Motor

Connector: DA15-F

D-Sub, 15 ways, female

image.png






 

1  Phase B2
2  Phase B1
3  Phase A2
4  Phase A1
5  Limit 1
6  Limit 2
7  Thermocouple negative
8  Thermocouple positive
9  GND
10
11
12
13 RTD B2
14 RTD B1
15 RTD A

DANGER! Danger of electric arcing! Never plug or unplug the connector while powered! Plugging or unplugging motor while powered may damage or destroy the driver output stages.

Motor

Connection of the motor to the vacuum feedthrough, and vacuum feedthrough to the SMD4 is discussed in section Motor Wiring.

Limits
There are two limits inputs; they can be configured to stop the motor on one or both limits being triggered. A limit input is triggered by shorting it to 'GND', usually with a mechanical switch mounted on the mechanism that the motor is driving. Logic level signals, for example, from optical or hall effect sensors may also be used. 
Input polarity can be reversed to accommodate normally open or normally closed switches.

Limit 1 applies when the motor position counter is incrementing, and limit 2 applies when the motor position counter is decrementing.

Limits inputs include a pullup resistor. See section Limits for details.
Thermocouple

The thermocouple lead for motors equipped with the standard K-Type thermocouple should be connected here. If using a motor equipped with an RTD, this connection may be left open. Be sure to select the correct sensor type, see section Temperature sensor selection.

RTD

For motors equipped with an RTD instead of a thermocouple, make the RTD connection here. If the RTD is not required, leave the connections open.

Custom cables

Custom motor cables must be built to the following specification to ensure continued compliance with EMC standards and correct function.

General requirements:

  • Rated voltage >= 300 V rms, rated current > 1.5 A rms
  • Construction; twisted pairs plus overall screen. Foil screen plus drain wire (of same or greater cross sectional area as main cores) acceptable, foil plus braided screen better
  • Screen must be connected via as short a wire as possible to a ground pin (pins 9-11) on the connector, using insulated wire
  • Maximum cable length is limited by the resistance of the cores; total round trip cable resistance per phase should be kept to less than few ohms. Consult the cable manufacturers data for these details. Excessive cable length causes a reduction in phase voltage at the motor compromising speed/torque characteristics

Temperature sensors:

  • Use one twisted pair for the thermocouple
  • Use one twisted pair for RTD A and B1, and one lead from a second pair for B2

I/O

Connector: DE9-F

D-Sub, 9 ways, female

image.png

1 GND
2 Fault
3 Limit 1/positive
4 Enable
5 Step
6 Reset fault
7 Limit 2/negative
8 SDE COM
9 Direction

USB

Connector: USB-C

image.png


USB Type-C connection. The connection is reversible, and the plug may be inserted either way up.

The SMD4 appears as a virtual COM port when connected to the PC. No additional drivers are required. Configure and control the SMD4 using AML Device Control software, available as a free download from our website at https://arunmicro.com/documents/software/

Alternatively, use a terminal program, or your own application. AML supply a C# API, available on our website to help customers implement their own applications faster.

LAN

Connector: 8P8C RJ45

RJ45, 8 poles, 8 connections

image.png

 

RS232/485

Connector: 8P8C RJ45

RJ45, 8 poles 8 connections







 

1  Motor B2
2  Motor B1
3  Motor A2
4  Motor A1
5  Limit 1
6  Limit 2
7  Thermocouple negative
8  Thermocouple positive
9  GND
10
11
12
13 RTD B2
14 RTD B1
15 RTD A

Encoder


Front panel

Same ideas smd3

See mech of ds for smd4 connectors etc.

All the text about IMO connectors goes, as smd4 does not have them. see rb for pinouts

power - per smd3 manual with changes: fixed 48 v per datasheet, statement about  max 67 goes because smd4 is for fixed 48v, blue info bit goes.

The rest just copy per smd3, but with substitute the new connectors

No thermocouple connector as now in motor connector, so move that section there

There are new connectors; 2 x rj45 for rs232/485 and 1 x rj45 for ethernet. Leave template sections for now.

Motor wiring; all change, leave empty section for now

Lead identification stuff remains same, as does wiring, cable stripping beads, cable requirements etc, rb to edit once template is in

Rear Panel


Power

x

Motor

x

I/O

x

Motor wiring

Overview

x

Lead identification

The motor leadout wires are self-coloured polyimide film-wrapped, silver-plated OFHC solid copper and each is fitted with a 1.5 mm crimp socket terminal. They are supplied fitted with UHV compatible coloured glass beads for identification. The phase leadout wires are much thicker than the thermocouple leadouts. The leadout wires of each phase should be twisted together.

motor leadout wires illustration_2.png

Motors equiped with a Thermocouple: Motors equiped with an RTD:
motor leadout wires TC illustration.png motor leadout wires RTD illustration.png

If the identification beads have been removed, the wires can be identified using an inexpensive multimeter, and a magnet. The multimeter must be capable of measuring resistance with a resolution of about 1 ohm.

Thermocouple Leadouts

The thermocouple wires are much thinner than the phase leads, and there are two of them. If three wires are present, the motor has an RTD installed, see below for details. The thermocouple is insulated from the rest of the motor. 
The two leads are of different material; one is made from Alumel, which is weakly magnetic, and the other Chromel, which is not. Use a magnet to find the Alumel wire, then connect as shown below.

 

Lead Connected to terminal marked
Alumel Alumel, N, - (minus) or coloured blue
Chromel Chromel, P, + (plus) or coloured brown  

RTD Leadouts

As per the thermocouple leads, but three instead of two leads. These must be identified by resistance; one pair of wires are connected at the motor end. These will measure a few ohms depending on cable length and are the ‘B1’ and ‘B2’ connections, which are interchangeable. The remaining wire is the ‘A’ connection and should measure around 100 ohms to either ‘B1’ or ‘B2’. 

 

Lead Connected to terminal marked
A A, or coloured blue
B1 Chromel,B1, or coloured brown  
B2 B2, or coloured brown

Phase leadouts
These are the four thicker leadouts. Identify the two motor phases by their resistance, which will be in the range of 3 to 15 ohms, depending on the motor type. There is no electrical connection between the two phases, to the thermocouple/RTD or the case of the motor. Most of the resistance is in the windings of the motor and is virtually unaffected by shortening of the leads. Connect each phase to the appropriate drive terminals. The resistance of the wires from the feedthrough to the drive must be less than a few ohms.

Note regarding reversal of rotation

Upon completion of wiring, there is a 50 % probability that the direction of rotation will be reversed from the desired or conventional sense. To rectify this, exchange the connections to one of the phases. For example, locate the Phase A + and Phase A – connections, and swap them around. This can be done on air or vacuum side while the chamber is still open.

Wiring motor to the vacuum feedthrough

The MLF18F feedthrough has 18 x 1.5 mm gold-plated feedthrough pins and is suitable for up to three motors fitted with thermocouples or up to two motors fitted with 3-wire RTDs. An internal bakeable connector, MLF18VCF, is available into which the crimp terminals on the motor leads are inserted. This significantly reduces the risk of short-circuits and makes the installation more convenient.

Using the MLF18F feedthrough and MLF18VCF vacuum side connector: Alternatively, plug crimps directly onto the feedthrough pins of the MLF18F:

vacuum side motor connection mlf18vcf.png

 

 

 

vacuum side motor connection straight into mlf18f 3.png

Mating side identified by dot. Motor lead terminals should be inserted in the other side.
Standard pinout for the MLF18VCF
The illustration below shows the view into the non-mating side of the connector, into which the motor leads should be inserted, as shown below.
Connection Colour Motor 1 Motor 2
Phase A1 Green 1 7
Phase A2 Grey 3 9
Phase B1 Black 2 8
Phase B2 White 4 10
Thermocouple + Brown 5 11
Thermocouple - Blue 6 12
RTD A Blue 13 16
RTD B1 Brown 14 17
RTD B2 Brown 15 18
mlf18ac pinning.png

Using other feedthroughs
AML stepper motors can be ordered with either a K-Type thermocouple, or 3-wire PT100 RTD. The former requires 6 pins, and the latter 7 pins. 

When using motors installed with a thermocouple, it is not necessary to use a thermocouple vacuum feedthrough or extension wires, as the error introduced by incompatible feedthrough material is usually less than 5 °C and the temperature measurement is not required to be very precise.

Preparation of motor leadouts for connection to other feedthroughs

If making custom terminations for the motor leads, the installed crimps must be removed, and the wire ends stripped of insulation. Standard motors are fitted with Polyimide film-wrapped leads (illustrated below), and radiation-hard motors are fitted with polyimide enamelled leads.

 

Polyimide is strong, flexible and abrasion-resistant and therefore difficult to strip. The simplest method of stripping polyimide film is to cut a ring with a sharp knife and withdraw the cylinder of insulation over the end of the wire. 

Be careful not to mark the conductor surface with the knife. Strip the enamelled radiation-hard leads by scraping with a sharp knife. Either type of lead may be stripped with a suitable high-speed rotary stripper. Do not use a thermal stripper.  

polyamide wire stripping.png

Wiring between drive and vacuum feedthrough

AML supply the MLF18SMD3 lead for use with the SMD3 and MLF18F feedthrough. It allows connection of up to two drives and motors installed in one vacuum chamber. Alternatively, AML supply the MLF18AC; which can be used to make custom leads to mate with the MLF18F feedthrough. This is supplied with a kit that includes the crimps and a grounding lead attached to the connector shell, as well as instructions for their use. The SMD3 is supplied with a kit of matching connectors.

Leads between the MLF18AC and SMD3 should be assembled according to the following guidance for safe, reliable operation and continued compliance with EMC standards.

Cable requirements

  • Quantity of cores as required; (one motor requires 6 cores when fitted with a thermocouple, or 7 if fitted with an RTD). The cable must be screened. A foil screen plus drain wire is acceptable; a foil plus braid screen is better.
  • The screen must be connected via as short a wire as possible to pin 1, ‘GND’ of the motor connector, using insulated wire.
  • Rated voltage >= 300 V rms
  • Rated current > 1.5 A rms
  • Cable cores must be twisted together in pairs, using one pair per phase, one pair for the thermocouple, and a group of three for the RTD. This reduces radiated emissions from the cable and improves immunity of the RTD and thermocouple signals to the motor.
  • Maximum cable length is limited by round trip resistance, which should be less than a few ohms. Review cable manufacturers data to obtain this figure.

Wiring up to the MLF18AC airside connector

The MLF18AC is supplied with comprehensive instructions detailing correct usage of the connector. The pinout to match with the standard MLF18F + MLF18VCF pinning described in section Motor wiring is shown below. Note that the illustration shows the MLF18AC looking into the non-mating side of the connector, i.e. the side into which crimps are inserted.


Connection Colour Motor 1 Motor 2
Phase A1 Green 1 7
Phase A2 Grey 3 9
Phase B1 Black 2 8
Phase B2 White 4 10
Thermocouple + Brown 5 11
Thermocouple - Blue 6 12
RTD A Blue 13 16
RTD B1 Brown 14 17
RTD B2 Brown 15 18

 

Looking into the non-mating face of the MLF18AC, into which crimps are inserted

mlf18ac pinningA.png
Wiring up to the SMD3
The cable shield must be connected to X2 (Motor connector), pin 1, GND, as described in the ‘Cable requirements’ section above.

Wire the motors leads to X2 (Motor connector) following the pinout shown in section X2-Motor.

For a motor installed with a thermocouple, split off the thermocouple leads close to the SMD3, keeping them twisted together and install in the thermocouple connector provided, following the pinout shown in section X4-Thermocouple.

For a motor installed with an RTD, split off the three RTD leads close to the SMD3, keeping them twisted together, and wire into the RTD A (pin 4), RTD B1 (pin 3) and RTD B2 (pin 2) positions of X3 (I/O connector), see section X3-I/O